AC 800F – The Field Controller
The ABB DCS AC 800F controller distributes process and diagnostic data from four fieldbus gateways. If required, it can also work with various fieldbus types – and this is, of course, in addition to the usual tasks of a "conventional" controller. Thanks to its compact and sturdy design, the AC 800F is suitable both for installation in the control room and for use in junction boxes directly in the field.
Economical and reliable into the future
AC 800F offers new possibilities, combining "easy engineering" with an open and modern system architecture:
- Availability: Redundancy at all levels
- Freedom of Choice: PROFIBUS, FOUNDATION Fieldbus or HART; or combinations of those protocols
- Efficient Engineering: Support for FDT/DTM
- Only one tool for engineering, commissioning and diagnositics
- Asset Optimization and batch processing
- System engineering covers fieldbus and device configuration
- On-board web server for remote diagnostics
Technical Data |
ABB DCS |
---|---|
CPU |
32-bit super-scalar RISC processor with high-speed bit processing |
RAM |
4 Mbyte (SRAM) or 16 Mbyte (DRAM) with internal or external battery backup 4 Mbyte Flash EPROM |
Environmental conditions | Ambient temperature: 0…60 °C Degree of protection: IP 20 |
Dimensions | 239 x 202 x 164 mm (W x H x D) Mounting on DIN rail |
Power supply |
120 / 230 V AC 24 V DC, redundant Power consumption: 30 VA max. |
Approvals | CSA-UL, CE, NAMUR |
AC800F Ordering information
AC800F Part No. | Parameters | IN STOCK |
FIELD CONTROLLER MASTER UNIT |
|
Check Stock |
PM802F | Include rack , CPU,8M | Check Stock |
PM803F | Include rack , CPU,16M | Check Stock |
POWER SUPPLER |
|
Check Stock |
SA811F | Field control equipment 220VAC-24VDC | Check Stock |
SD812F | Field control equipment 24VDC-24VDC | Check Stock |
Ethernet module |
|
Check Stock |
EI811F | 10Base2 Module | Check Stock |
EI812F | AUI Module | Check Stock |
EI813F | 10Base T Module | Check Stock |
Other communication module |
|
Check Stock |
FI810F | CAN Module | Check Stock |
FI820F | Modbus Module | Check Stock |
FI830F | Profibus-DP V1 Module | Check Stock |
FI840F | FF Module | Check Stock |
Accessory |
|
Check Stock |
TK807F | SA801F/SA811F service cable | Check Stock |
TK808F | SA801F/SA811F service cable,Eur standard plug | Check Stock |
TK809F | SA801F/SA811F service cable,USA standard plug | Check Stock |
TK802F | SD802F service cable | Check Stock |
TK821F | Serial interface communication cable,0.5m | Check Stock |
TK831F | CAN communication cable,0.5m | Check Stock |
TK811F | CAN communication cable,3m | Check Stock |
TK817F | CAN communication cable,100m | Check Stock |
TK890F | Diagnosis cable 5m | Check Stock |
TK891F | Diagnosis cable 10m | Check Stock |
TB870F | Communication wiring board | Check Stock |
AM811F | Battery module | Check Stock |
AM895F(4) | Front panel(4pcs in one bag) | Check Stock |
SB808F | RAM back up battery (for EI8**Fmodule) | Check Stock |
SY809F | Battery stents | Check Stock |
The ABB DCS AC 800F hardware
The ABB AC 800F has a modular structure. The AC 800F CPU is designed as a
backplane to which various modules – power supply units, Ethernet or
fieldbus modules – can be attached in line with the application. On the
fieldbus side, modules for PROFIBUS-DPV1, FOUNDATION Fieldbus HSE,
MODBUS (master/slave, RTU or ASCII), IEC 608 0-5-101 and CAN for
Freelance Rack I/O are available. The fieldbus line and the connected
PROFIBUS slaves are entirely configured and parameterized using the
Control Builder F engineering tool. No further external tools are needed
for configuration. PROFIBUS slaves can be integrated into the system
using a GSD) file or FDT/DTM). In the case of FOUNDATION Fieldbus,
configuration takes place using CFF or DD files. This allows fieldbus
parameterization even without connected field devices.
Also Freelance Rack I/O can be connected to the ABB AC 800F, in which
case a CAN module is used. This allows you to operate five I/O racks,
with a total of around 1000 I/Os, for each AC 800F. The I/O racks are
equipped with a link module and up to nine I/O modules and can be
mounted separately at a distance of up to 400 m from the AC 800F.
AC 800F Fieldbus modules
The ABB AC 800F uses the fieldbus modules to collect and process
real-time and diagnostic data. Up to four fieldbus modules can be
mounted into one AC 800F.
The fieldbus modules have the following tasks and
characteristics:
• Electrical isolation between the process and system
• Status LEDs for the module status
• Independent fault detection and fault signaling
• Connection of the fieldbus lines
Details of the fielbus modules | ABB CH | ABB PLC |
---|---|---|
Type | Channels | Function |
CAN module | 1 | Connection of up to 5 Freelance I/O racks |
Serial module | RS /RS4 /RS485 configurable for MODBUS, IEC 608 0-5-101 telecontrol protocol | |
PROFIBUS module | 1 | Full-value PROFIBUS DPV1 Master |
FF-HSE module | 1 | For the connection of up to 10 LD 800HSE Linking Devices with 10/100 MBaud autosense twisted pair connection |
Ethernet modules
Process stations and the operator and engineering level in the Freelance system communicate with each other via Ethernet.
Ethernet modules for the system bus | ||
---|---|---|
Type | Channels | Function |
Ethernet module | 1 | Twisted pair connection 10 base T for connection to hubs or switches |
Ethernet module | 1 | BNC connection 10 base for thin coaxial cable (Cheapernet), 10 MBit/s |
Ethernet module | 1 | AUI connection 10 base 5 and 10 base FL via coupler |
ABB AC 800F Engineering
ABB AC 800F control applications can be created in any of the five IEC 61131-3 dialects by using Control Builder F.
see Engineering Tool Control Builder F
ABB AC 800F functional range
The ABB AC 800F scope of functions provided by the Freelance system
corresponds to the basic supply defined in IEC 61131-3, in addition to
numerous other high performance, industry-proven functions and function
blocks. They are accommodated in a function block library and can be
supplemented by user-specific function blocks. While designing the
station and during configuration, the processing capacity and speed of
the process station can be easily adapted to the demands of the
automation task. Program execution in the process station is based on a
task-oriented, real-time multitasking operating system, leading to a
flexible strategy for processing programs.
Different modes are available for task execution:
- Cyclical processing with cycle times from 5 ms upward
- Fastest-possible processing (PLC mode)
Along with the user tasks, system tasks – in which functions can also be processed – are automatically made available. These tasks are executed once in case of the following events:
- RUN
- STOP
- COLD START
- WARM START (voltage restored)
- REDUNDANCY TOGGLE
- ERROR
Up to eight cyclic user tasks and one PLC mode task can be configured in a process station.
Functions and Function Blocks | |
Analog value processing AC800F FUNCITIONS |
|
Binary value processing |
|
Closed-loop control |
|
Open-loop control |
|
Logic functions |
|
Monitoring |
|
Acquisition Arithmetic functions |
|
Modbus functions PROFIBUS |
|
FOUNDATION Fieldbus (FF) Send/Receive |
|
Phase logic processing |
|
Intelligent linking devices
As the AC 800F possesses the high-speed connection of both PROFIBUS
(PROFIBUS DP) and FOUNDATION Fieldbus (FF-HSE), the slower buses of the
two fieldbus technologies (PROFIBUS PA and FF-H1) can be connected using
intelligent linking devices.
These devices allow to connect several slow buses to one fast bus, with
the advantage that a lot more field devices can be connected to an ABB
DCS AC 800F station than when the slow fieldbuses are connected
directly.
Maximum Security
In order to achieve safe operation and high plant availability,
the ABB DCS AC 800F supports redundancy on all levels. This increases
security and avoids production downtime! Redundancy is available for
the:
- System bus (Standard Ethernet Solution)
- Controller
- Input/output modules
- Fieldbus master
- Fieldbus lines
- Linking devices
- HSI communication
High Flexibility
Digital communication has changed automation technology to the
better. Fieldbus technology is nowadays proven and well accepted by the
users to perform the tasks of transmitting process- as well as
diagnostic data. This is an enabling technology for new applications
such as asset optimization
ABB AC 800F collects and processes signals and diagnostic data from up to four fieldbus lines. If required, it can also simultaneously work with various fieldbus types – and this is, of course, in addition to the usual tasks of a “conventional” process station. Furthermore, the ABB DCS AC 800F has a compact and modular design which makes it a universal electronic component for virtually all types of applications. It is suitable for both: simple installation in the switch room and for direct use in the field. Take the advantage provided by this technology:
The ABB DCS AC 800F allows you to use the fieldbus type(s) which best meets your requirements:
- PROFIBUS
- Foundation Fieldbus
- MODBUS protocol
- Interbus
- IEC 870-5 telecontrol protocol
- CAN-Bus for connecting Input/Output modules
- HART with PROFIBUS remote I/O
Efficient Engineering
For consistent configuration, commissioning and diagnosis – from
graphics to the field device – you only need one engineering tool. This
tool supports fieldbus-specific
configuration in the familiar way by means of its consistent, system-wide database. This includes:
- Configuration and parmeter setting of field devices and remote I/Os via GSD/GSE files or FDT/DTM
- Integrated diagnostics for controller and device checks with automatic alarms
- Automatic generation of displays for operation
- Bus topology and parameters such as transmission rates and addre