Your Position: Home > Brand > PEPPERL+FUCHS

KFD2-CD-Ex1.32 Current/Voltage Driver

Update: 2016/5/19      View:
  • Brand:    PEPPERL+FUCHS
  • Type:    
  • Order Online
Introduction
• 1-channel isolated barrier
• 24 V DC supply (Power Rail)
• Current/voltage output up to
850 Ω/3 Ω load
• Factory configured input/output
• Accuracy 0.1 %
• Up to SIL2 acc. to IEC 61508
Function
This isolated barrier is used for intrinsic
safety applications. It drives a voltage or
current signal from the safe area to I/P
converters, electrical valves and
positioners located in the hazardous
areas.
According to a unique ordering code, this
barrier is designed to provide various

inputs and outputs of voltage and current.

Ordering example: Input 0 V ... 10 V and output 4 mA ... 20 mA is code number 8
Model number is KFD2-CD-Ex1.32.8
The values shown in parentheses are subsets of the larger signal range.
Supply
Rated voltage 20 ... 35 V DC
Input
Voltage drop Ud optional current input: approx. 4 V at 20 mA
Limit optional current input: input current: approx. ≤ 40 mA
optional voltage input: input voltage: 12 V DC
Transmission range optional current input: 0 ... 20 mA/
optional voltage input: 0 ... 10 V
Output
Current optional current output: 0 ... 20 mA/optional voltage
output: ≤ 20 mA
Load optional current output: ≤ 850 Ω
optional voltage output: output resistance ≤ 3 Ω
Voltage optional current output: 17 V at 20 mA/
optional voltage output: 0 ... 10 V
Ambient conditions
Ambient temperature -20 ... 60 °C (253 ... 333 K)
Mechanical specifications
Protection degree IP20
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in), housing type B1
Data for application in conjunction
with hazardous areas
see page 248 for entity parameters
EC-Type Examination Certificate BAS 02 ATEX 7203
Group, category, type of protection ¬ II (1)GD [EEx ia] IIC (-20 °C ≤ Tamb ≤ 60 °C)
Statement of conformity TÜV 99 ATEX 1499 X
Group, category, type of protection,
temperature classification
¬ II 3G EEx nA II T4
FM control drawing 116-0129
UL control drawing 116-0173 (cULus)
CSA control drawing 116-0132