Allen Bradley 1756-ENBT ControlLogix EtherNet/IP Bridge Module

Update: 2017/10/24      View:
  • Brand:    Allen Bradley
  • Type:    
  • Order Online
Introduction
Specifications
Module Location Any slot in the ControlLogix chassis
Backplane Current (mA)
at 5V.1V dc
700mA
Backplane Current (mA)
at 24V
3mA
Isolation Voltage,
Continuous
30V
Tested to 707V dc for 60 seconds
Power Dissipation, Max. 3.65W
Conductors
Wire Size
Category
802.3 compliant - shielded or unshielded twisted pair
21
Ethernet Connector RJ45 Cat. 5
User Manual ENET-UM001
Environmental Conditions
Operating
Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
Storage
Temperature
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):
–40 to 85°C (–40 to 185°F)
Relative
Humidity
IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp
Heat):
5 to 95% non-condensing
Vibration IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz
Shock,
Operating
IEC60068-2-27 (Test Ea, Unpackaged shock):

30g


Publication 1756-IN019C-EN-P - November 2004
Shock,
Non-operating
IEC60068-2-27 (Test Ea, Unpackaged shock):
50g
Emissions CISPR 11:
Group 1, Class A
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF
Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on communications ports
Surge
Transient
Immunity
IEC 61000-4-5:
±2kV line-earth(CM) on communications ports
Conducted RF
Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Enclosure Type
Rating
None (open-style)

Certifications2
(when product is
marked)
UL UL Listed Industrial Control Equipment
CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment for Class I,
Division 2 Group A,B,C,D Hazardous Locations
FM FM Approved Equipment for use in Class I Division 2
Group A,B,C,D Hazardous Locations
CE European Union 89/336/EEC EMC Directive, compliant
with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx European Union 94/9/EEC ATEX Directive, compliant
with:
EN 50021; Potentially Explosive Atmospheres,
Protection “n” (Zone 2)
EtherNet/IP ODVA conformance tested to EtherNet/IP
specifications

Prepare the Chassis for Module Installation
Before you install the module, you must install and connect a ControlLogix
chassis and power supply.
For information on installing these products, refer to the publications listed
below.
Chassis
Type
Chassis
Installation
Power
Supply
Power Supply
Installation
Series B: 1756-A4, -A7, -A10, -A13 Pub. No.
1756-IN080
1756-PA72/B Pub. No.
1756-5.67
1756-PB72/B
1756-PA75/A Pub. No.
1756-5.78
1756-PB75/A
20805-M
1756-A4
Chassis
Power
Supply


More Products